KIT | KIT-Bibliothek | Impressum | Datenschutz

IEC 61850 traffic at ANSI 87T differential protection attacks

Fruböse, Clemens ORCID iD icon 1; Fruböse, Clemens ORCID iD icon 1; Seiquera, John 2
1 Institut für Informationssicherheit und Verlässlichkeit (KASTEL), Karlsruher Institut für Technologie (KIT)
2 Institut für Automation und angewandte Informatik (IAI), Karlsruher Institut für Technologie (KIT)

Abstract:

During GNSS attacks on a time server in an electrical substation, the time service is affected and, accordingly, time-critical protection functions can misoperate. In our threat model, these trips are maliciously triggered via time synchronization attacks (using the so-called two-clock GNSS attack). These data show how IEC 61850 Sampled Values, IEEE 1588 Precision Time Protocol, and GOOSE traffic behave under these attacks, with GOOSE messages proving the misoperation of the differential protection IED.
This is the complementary dataset for the paper: "Malicious GNSS Spoofing Causing False Trips in IEC 61850 Multivendor Substations" by Fruböse et al. (2026).


Download
Originalveröffentlichung
DOI: 10.35097/prcfrppz0c1f1e28
Zugehörige Institution(en) am KIT Institut für Automation und angewandte Informatik (IAI)
Institut für Informationssicherheit und Verlässlichkeit (KASTEL)
Publikationstyp Forschungsdaten
Publikationsjahr 2026
Identifikator KITopen-ID: 1000198071
HGF-Programm 46.23.02 (POF IV, LK 01) Engineering Security for Energy Systems
Lizenz Creative Commons Namensnennung – Nicht kommerziell 4.0 International
Schlagwörter Information Technology, IEC 61850, IEC/IEEE 61850-9-3, IEC 61850-9-2, Precision Time Protocol (PTP), Sampled Values (SV), GNSS spoofing, Digital substation cybersecurity, Time Synchronization, IEC 61869-9
Art der Forschungsdaten Dataset
Nachgewiesen in OpenAlex
Rechteinhaber Karlsruhe Institute of Technology